• Control panel with 1 or 2 loops.
• Loop capability 226 points.
• Capacity for 64 relays per loop and 128 in total.
• Allows A50xxLD detectors with visual and sound alarm notification.
• Search for loop points in sequential order according to their physical position on the cable.
• Programming of 99 zones.
• Registry with capacity of 6601 events.
• Relay configuration with activation of 1, 2 or 3 alarm detectors.
• Relay trigger auto-configuration function.
• 2 independent programmable sounder outputs.
• 2 auxiliary 30V output connectors with programmable reset.
• Alarm output as an unmonitored voltage-free relay.
• Fault output, delayed and monitored.
• Allows addressable acoustic and visual sounders to be connected to the loop.
• Evacuation push button.
• Backlit LCD display with 4 lines and 40 characters.
• It incorporates several languages by default (Spanish, English, French, Portuguese, etc.).
• Configurable via PC software, I-Link.
• Event management with facility drawings using PC software, I-Link online.
• Access to the panel keypad using a numeric code.
• Connection of up to 15 repeaters and/or 15 network control panels.
• Cofem 360, CRI and MODBUS functionality on demand.
• Dimensions: 363 x 331 x 96 mm (with cover).
• UL/EU certification according to Standard EN 54 Part 2 and EN 54 Part 4, and CE marking according to European Construction Products Regulation (EU) No. 2024/3110.